VFTO引起的500kV电缆金属护层感应过电压研究
Induced Overvoltage of Cable Metal Sheath in 500 kV Pumped Storage Power Station Under VFTO Condition
摘要
抽水蓄能电站因建设环境限制,需大量使用GIS设备,GIS结构紧凑的特点提高了抽水蓄能电站特快速暂态过电压(VFTO)发生的概率,由VFTO引发的进线电缆护层感应电压过大导致危害设备安全及工作人员人身安全的情况必须得到重视.为此,首先通过仿真得到抽水蓄能电站进线段电缆护层感应电压特性,并明确了电缆护层感应过电压保护的必要性.其次,针对电缆护层过电压抑制方案进行仿真验证.最后,根据仿真结果,证明所提方案有效性,并提出方案选择优先级,为抽水蓄能电站进线段电缆防护措施的选择提供参考.
Due to the constraints of the construction environment of pumped storage power stations,a large number of GIS equipment is required.The compact structure of GIS increases the probability of VF-TO occurrence.The induction voltage of the incoming cable sheath caused by the VFTO is too large,which endangers the safety of equipment and the personal safety of workers.Therefore,firstly,the in-duced voltage characteristics of the inlet cable of pumped storage power station are obtained through simu-lation,and the necessity of induced overvoltage protection of the cable sheath is clarified.Secondly,the overvoltage suppression scheme of cable sheath is verified by simulation.Finally,the simulation results prove that the proposed schemes.Further,we propose the priority of scheme selection,which provides support and reference for the selection of cable protection measures in the inlet section of pumped storage power station.