电容电流超标变电站的弧光过电压幅值及影响因素研究
Amplitudes and Influencing Factors of Arc Grounding Overvoltage for Substations with Excessive Capacitance Current
摘要 近年来我国配电网电容电流逐渐增大,中性点消弧线圈容量面临限制,无法保证可靠熄弧.对电容电流超标的中性点不接地配电网中弧光过电压的幅值和影响因素进行研究,有助于评估过电压威胁,提出合适的大电容电流配电网的中性点接地方式,实现高准确率的单相接地故障识别和选线.基于我国配电网的发展历程,搭建了几种具备不同出线参数的大电容电流 10 kV变电站模型,仿真计算不同故障工况下的弧光过电压幅值,其中考虑包括故障点过渡电阻、故障点位置和电容电流等在内的共 6 个因素的影响.结果表明,电容电流超标的变电站不会出现幅值高于3.5 p.u.的弧光接地过电压,并且过电压幅值主要与故障点过渡电阻、故障点位置和故障相位等有关.
Abstract:
In recent years,the capacitance current of distribution networks in China has gradually in-creased.The capacity of neutral arcing coil is limited,and the reliable arc extinguishing cannot be guar-anteed.Research on the amplitude and influencing factors of arc overvoltage in ungrounded distribution network with excessive capacity current can help to assess the threat of overvoltage,propose suitable neu-tral grounding modes for large capacitance current distribution networks,and achieve high accuracy in i-dentifying and selecting single-phase grounding faults.Based on the development history of distribution networks in China,several 10 kV substation models with large capacitance current equipped with different line parameters are constructed to simulated the arc overvoltage values under different situations,consid-ering the influence of 6 factors including fault transition resistor,fault location and capacity current,etc.The results show that substations with excessive capacitance current will not experience arc grounding ov-ervoltage with amplitudes greater than 3.5 p.u.,and the arc overvoltage value is mainly related to the fault transition resistor,fault location and fault phase.
刊 名 电瓷避雷器
年,卷(期): 2026, (5)
机标分类号: TM727 TM862 TM475
在线出版日期: 2026年11月9日