转子接地保护原理对比分析及抗跳变优化研究
Comparative Analysis and Maloperation Resistance Optimization Study of Rotor Earth Fault Protection Principles
摘要
针对大型水电站发电机转子接地保护因电阻跳变引发误动或拒动的技术瓶颈,本文深入剖析了工程中主流应用的PCS-985 型乒乓式与注入式保护原理,构建了接地电阻及接地点位置的计算模型,结合发电机转子接地电阻异常波动的实际案例进行分析,总结出影响转子接地电阻测量准确性的主要因素及解决办法.研究成果可为发电机组保护系统可靠性提升提供有效解决方案,且可推广应用于风电、核电等新能源装备领域.
Aiming at the technical bottleneck of misoperation or failure to operate caused by grounding resistance fluctuation in the rotor grounding protection of generators in large hydropower stations,this paper conducted an in-depth analysis of the widely used PCS-985 ping-pong and injection protection principles.A calculation model for grounding resistance and fault location was established.Combined with actual cases of abnormal grounding resistance fluctuation in generator rotors,the main factors affecting the measurement accuracy and their solutions were summarized.The research results provide an effective solution for improving the reliability of generator protection systems and can be extended to fields such as wind power and nuclear power equipment.