军事知识服务平台
500kV GIS开关液压机构油泵频繁启停故障诊断与优化研究
Fault Diagnosis and Optimization for Frequent Starting and Stopping of the Oil Pump in the 500 kV GIS Switch Hydraulic Mechanism
摘要 500 kV GIS开关液压机构作为电力系统关键操动单元,其运行稳定性直接影响电网暂态安全与供电可靠性.本文针对A水电站GIS开关分合闸后B相液压机构油泵打压周期骤缩至2.9h的异常现象,对其进行了分析,构建了含内漏、进气的压力动态模型,结合多维度验证与MATLAB仿真,明确了可恢复性内漏与进气是造成该油泵打压周期异常的核心原因,并提出了"油液净化+阀组修复+阶梯式排气"处理措施.现场验证表明,新措施实施后,油泵平均打压周期延至152 d,年度启停次数从343 降至 26,压力波动标准差从0.35 MPa降至0.08 MPa,油液清洁度维持NAS 6 级.本研究成果可为行业电站的同类问题解决提供参考.
Abstract:
The hydraulic mechanism of the 500 kV GIS(Gas Insulated Switchgear)switch,as a critical operating unit in the power system,directly determines the transient safety of the power grid and the reliability of power supply.This paper analyzes the abnormal phenomenon where the oil pump pressurization cycle of phase B hydraulic mechanism in the GIS switch of Hydropower Station A abruptly shortened to 2.9 hours per cycle after opening and closing.A dynamic pressure model incorporating internal leakage and air ingress was established.Through multi-dimensional verification and MATLAB simulation,it was clarified that recoverable internal leakage and air ingress are the core causes of this abnormal pressurization cycle.The proposed treatment measures include oil purification,valve assembly repair and stepwise air venting.Field verification confirmed that after implementing the new measures,the average oil pump pressurization cycle was extended to 152 days,annual start-stop cycles decreased from 343 to 26,pressure fluctuation standard deviation dropped from 0.35 MPa to 0.08 MPa,and oil cleanliness maintained NAS 6 grade.This research outcome provides reference for addressing similar issues in power stations within the industry.
刊 名 大电机技术 ISTIC
年,卷(期): 2026, (z1)
分类号: TM762
机标分类号: TM307.1 TP29 TU998.1
在线出版日期: 2026年3月11日