摘要
将R1233zd(E)与闪蒸罐蒸汽注入技术相结合可以提升制冷性能并弥补其容积制冷量偏低的不足.针对采用R1233zd(E)的闪蒸罐蒸汽注入制冷系统,建立了基于质量与能量守恒的热力学数学模型.当蒸发温度为-30~5℃,冷凝温度为20~40℃,一级压缩比为1.1~6.5时,系统计算并分析了性能系数(COP)、制冷量及压缩机功耗等参数的变化规律,同时构建了基于运行温度的最佳一级压缩比拟合方程.结果表明,系统COP随蒸发温度升高而增大,当冷凝温度为40℃,蒸发温度由-30℃升至5℃时,COP从约1.86提升至约4.53.COP随冷凝温度升高而降低,当蒸发温度为-20℃,冷凝温度由20℃升至40℃时,COP从约3.58降至约2.29.系统存在最佳中间压力以获得最大COP,推导出的最佳一级压缩比关联式与模型计算值的偏差主要集中在±3%以内,可为系统运行参数设定和智能控制提供理论指导.
Coupling R1233zd(E)with flash tank vapor injec-tion enhances refrigeration performance and compensates for its inherently low volumetric refrigeration capacity.A thermodynamic mathematical model based on mass and en-ergy conservation was developed for a flash tank vapor in-jection refrigeration system utilizing R1233zd(E).Key per-formance parameters,including the coefficient of perfor-mance(COP),cooling capacity,and compressor power consumption,were systematically analyzed across an evapo-ration temperature range of-30 to 5℃,a condensation tem-perature range of 20 to 40℃,and a first-stage compression ratio range of 1.1 to 6.5.Furthermore,a fitted equation for the optimal first-stage compression ratio was derived based on operating temperatures.Results indicated that the system COP increased with rising evaporation temperature.In par-ticular,at a fixed condensation temperature of 40℃,the COP increased from~1.86 to 4.53 as the evaporation tem-perature increased from-30 to 5℃.Conversely,the COP decreased with increasing condensation temperature;when the evaporation temperature was maintained at-20℃,the COP decreased from~3.58 to 2.29 as the condensation tem-perature increased from 20 to 40℃.An optimal intermedi-ate pressure existed for maximizing the system COP.The deviation between the values calculated by the derived corre-lation for the optimal first-stage compression ratio and the theoretical model was predominantly within±3%.This pro-vided theoretical guidance for operational parameter setting and intelligent control of the system.