新能源送出线路两相接地故障距离保护动作差异机理分析及对策
Mechanism Analysis of Distance Protection Different Actions for Two Phase Ground Faults in Grid-connected Renewable Energy Transmission Lines and Countermeasures
摘要 新能源交流送出线路发生两相接地故障时,以正序电压为极化量的相间距离保护和接地距离保护动作行为存在差异,表现为相间距离保护在区内故障时可能拒动,在区外故障时可能误动;但接地距离保护在区内外故障时均正确动作.理论分析了正序电压极化距离保护正确动作的边界条件,揭示了新能源送出线路两相接地故障后,相间距离保护不正确动作机理:受新能源电源控制响应影响,相间距离保护判据中零序电流分量缺失导致故障后正序电压相位无法准确反映故障前新能源电源等效内电势的相位,工作电压与极化电压相位差增大,突破保护正确动作边界.在此基础上,为防止区内外故障保护不正确动作,提出了相间距离保护改进策略.利用实时数字仿真平台(real time digital simulator)建立了新能源送出线路仿真模型,验证了理论分析正确性及改进策略的有效性,提升了新能源送出线路距离保护性能.
Abstract:
When two phase ground faults occur in grid-connected renewable energy transmission lines,the action behavior of positive sequence voltage polarization phase-to-phase distance protection and earthing-fault distance protection are different.Phase-to-phase distance protections may refuse to operate for internal fault and mis-operate for external fault,but earthing-fault distance protections act correctly.The paper analyzes the correct action boundary of positive sequence voltage polarization distance protection and reveals the mechanism of incorrect operation of phase to phase distance protection.Affected by the control response of new energy power sources,the absence of zero sequence current component in the phase to phase distance protection criterion leads to the inability of the positive sequence voltage phase to accurately reflect the phase of the equivalent internal potential of the new energy power source before the fault,resulting in an increase in the phase difference between the working voltage and the polarization voltage,breaking through the boundary of correct protection action.On this basis,a distance protection improvement strategy is proposed to prevent incorrect operation of phase-to-phase distance protection.A simulation model of grid-connected renewable energy transmission lines was established using the Real Time Digital Simulator,which verified the correctness of theoretical analysis and the effectiveness of improvement strategies.The simulation results show that improvement strategies can improve the distance protection performance of grid-connected renewable energy transmission lines.