基于再生水的冰源热泵集中低温供热系统特性研究
Research on the characteristics of ice source heat pump central low-temperature heating system based on recycled water
摘要
我国北方供热碳排放量大,传统污水源热泵在低温下效率低,难以充分提取再生水低品位热能.冰源热泵可利用水-冰相变潜热供热,极寒环境下运行潜力突出,但工程应用研究不足.本文以雄安新区再生水厂冰源热泵中试平台为对象,搭建制热-制冰-蓄冷协同系统,研究变预热温度、过冷水流量及压缩机负载下的供热特性.结果表明:供热量与主机能效随预热温度升高而提升,过冷水流量168 m3/h、预热温度1.6℃时,系统综合能效达峰值3.03;压缩机50%~80%负载区间供热快速上升,系统综合能效稳定在3.15~3.22,变负荷适应性优异.过冷度与含冰率正相关,可通过参数调控优化换热与防冰堵.
Heating in northern China generates large carbon emissions,and conventional sewage-source heat pumps suffer from low efficiency at low temperatures,making it difficult to fully extract low-grade heat from reclaimed water.Ice-source heat pumps can provide heating by utilizing water-ice phase change latent heat and show outstanding operational potential in ex-tremely cold environments,yet research on their engineering applications remains insufficient.Taking an ice-source heat pump pilot platform at a reclaimed water plant in Xiong'an New Area as the object,this paper establishes a collaborative system of heating,ice-making and cold storage,and investigates its heating performance under varied preheating temperatures,subcooled water flow rates and compressor loads.The results show that heating capacity and unit energy efficiency increase with rising pre-heating temperature;the system achieves a peak comprehensive COP of 3.03 at a subcooled water flow rate of 168 m3/h and a preheating temperature of 1.6 ℃.Heating output rises rapidly in the 50%~80%compressor load range,and the system's com-prehensive COP stays stable at 3.15~3.22,indicating excellent partial-load adaptability.Subcooling degree is positively corre-lated with ice content,and heat transfer and anti-icing performance can be optimized through parameter regulation.
年,卷(期):
2026, 54(7)
分类号:
TK02
机标分类号:
TU833.1
TU995
TK123
在线出版日期:
2026年8月20日
基金项目:
2021YFE0112500:国家重点研发计划,