A Spatiotemporal Two-layer Optimization Model for Distributed Photovoltaic Accommodation in Rural Distribution Networks
摘要
针对村镇配电网分布式光伏大规模接入引发的消纳受限与反向重载问题,传统源储协同方法因成本高昂难以落地,为此,提出一种基于需求响应与网络重构的时空双层协同消纳策略.首先,对村镇配电网的源荷时空分布特征以及消纳瓶颈进行分析,并将其建模为相应的运行约束;其次,在时间维度构建台区需求响应模型,利用深谷电价引导农业排灌等可转移负荷实现时序转移;最后,在空间维度计及开关动作频次、辐射状拓扑等约束,构建网络重构模型,实现高光伏区向重载区的跨区域功率疏导,并通过时空耦合优化确定最佳调度方案.采用河南某实际配电网开展算例分析,通过灵敏度分析明确多因素对模型消纳效益的影响,并选取最优参数.结果表明,该策略可将光伏消纳率提升至95.33%,日运行成本降低31.7%,能够有效缓解反向重载与过电压风险.
In response to the challenges of limited photovoltaic(PV)accommodation and reverse overloading caused by large-scale integration of distributed PV in rural distribution networks,while traditional source-storage coordination is difficult to be achieved due to high costs,this paper proposes a spatiotemporal two-layer coordinated accommodation strategy based on demand response and network reconfiguration.Conventional source-storage coordination methods are often impractical due to high costs.The proposed approach proceeds as follows:First,the spatiotemporal characteristics of source-load distribution and the associated accommodation bottlenecks in rural distribution networks are analyzed and formulated as operational constraints.Second,a time-domain demand response model at the distribution transformer area level is established,leveraging deep off-peak electricity pricing to temporally shift shiftable agricultural loads such as irrigation pumps.Third,a spatial-domain network reconfiguration model is developed,incorporating constraints on switch operation frequency and radial topology,to enable cross-area power flow redirection from high PV zones to heavily loaded areas.An integrated spatiotemporal optimization framework is then employed to determine the optimal dispatch schedule.The proposed strategy is validated using a real-world distribution network in Henan province.Sensitivity analysis quantifies the impacts of multiple factors on accommodation performance,facilitating the selection of optimal parameters.Simulation results demonstrate that the strategy increases the PV accommodation rate to 95.33%and reduces daily operational costs by 31.7%,effectively mitigating reverse overloading and overvoltage risks.