新能源电力系统的规模化并网使新能源场站变压器长期承受高频电应力,加剧变压器油纸绝缘的劣化,但高频电热耦合作用下的老化机制尚未明晰.为此,该研究搭建高频电热老化平台,对比了100 kHz高频与50 Hz工频电压加速老化对油纸绝缘宏观介电性能与微观化学结构劣化规律.结果表明:高频老化后,频域介电谱全频段介电损耗提高,104 Hz 附近出现弛豫峰,体积电阻率下降 3 个数量级,击穿电压尺度参数下降 53.5%、形状参数降低;正负极附近空间电荷密度大幅增加,且曲线呈多峰分布,扫描电镜观察到纤维广泛断裂及微米级孔隙;分子动力学模拟与红外光谱共同证实高频加速纤维素主链 C—C、C—O 键断裂及极性产物生成.研究揭示高频下极高的电压变化率加剧极化损耗与空间电荷注入,与热应力形成正反馈循环,导致缺陷累积、结构疏松化,从宏微观协同加速油纸绝缘劣化.研究结果为高频工况下新能源场站变压器油纸绝缘的状态评估与寿命预测提供参考.
The large-scale grid integration of renewable energy power systems subjects the transformers in renewable energy stations to prolonged high-frequency electrical stress,thereby accelerating the degradation of oil-paper insulation.However,the aging mechanism under the coupled electro-thermal effects of high-frequency conditions remains unclear.To address this,a high-frequency electro-thermal aging platform was established in this study,and the degradation be-haviors of macroscopic dielectric properties and microscopic chemical structure of oil-paper insulation under accelerated aging with 100 kHz high-frequency voltage and 50 Hz power-frequency voltage were compared.The results show that,after high-frequency aging,the dielectric loss across the entire frequency range in frequency domain dielectric spectros-copy increases,with a relaxation peak appearing near 104 Hz;the volume resistivity decreases by three orders of magnitude;the scale parameter of breakdown voltage decreases by 53.5%and the shape parameter also decreases;the space charge density near both positive and negative electrodes increases substantially,with a multi-peak distribution in the curve.Moreover,scanning electron microscopy reveals extensive fiber breakage and micron-scale pores.Molecular dynamics simulations and infrared spectroscopy jointly confirm that high frequency accelerates the breakage of C—C and C—O bonds in the cellulose main chain and the generation of polar products.This study reveals that the extremely high voltage change rate under high-frequency conditions intensifies polarization loss and space charge injection,forming a positive feedback loop with thermal stress,which leads to defect accumulation and structural loosening,thereby synergis-tically accelerating oil-paper insulation degradation from both macro and micro perspectives.The research results provide reference for the condition assessment and life prediction of oil-paper insulation in transformers at renewable energy sta-tions under high-frequency operating conditions.