Arc-discharging Test Method and Energy Release Characteristics Analysis for Oil-immersed Inverted Current Transformers
摘要
油浸倒立式电流互感器燃弧爆炸呈现高位破坏特性,碎片大范围高速溅射,对周边设备及人身安全形成冲击威胁.然而,IEC 61869-1/IEEE C57.13.5 仅提及互感器燃弧试验的基础框架,对于电弧参数、评判依据等核心环节尚未形成统一标准,导致各方试验开展差异化、结果缺乏可比性,约束了电流互感器燃弧试验体系的建设与完善.因此构建了"引弧埋设-防护体系-回路配置-防爆判据"的整体试验方案,分析了电流互感器燃弧爆炸动态过程.针对常规型器身薄弱环节进行了防爆片、连通路径等结构的试探性优化,并再次开展系列燃弧试验对比验证.试验结果表明,电流互感器燃弧爆炸过程分为骤压、蓄压、撕裂、爆炸这 4 个阶段,合理调配防爆片阈值与储油柜连接通道大小能显著降低能量释放水平,改进型电流互感器燃爆碎片飞溅范围降低了 48.4%,碎片比动能被限制在76 J/cm2以下.试验方法可为燃弧试验标准体系建设提供参考,试验结果可为电流互感器防爆性能提升提供理论依据.
Oil-immersed inverted current transformers exhibit high-level destructive characteristics during arc flash ex-plosions,with fragments ejected over a wide area at high velocity,posing a significant impact threat to surrounding equipment and personnel safety.However,IEC 61869-1/IEEE C57.13.5 merely outlines the fundamental framework for arc testing of instrument transformers.Core aspects such as arc parameters and evaluation criteria remain un-standardized,leading to divergent testing methodologies and non-comparable results.This hinders the development and refinement of a comprehensive arc testing system for current transformers.Consequently,we established a systematic testing protocol encompassing'arc initiation and containment-protective systems-circuit configuration-explosion criteria'.We analyzed the dynamic progression of arc flash explosions in current transformers.Exploratory optimizations of structural ele-ments,including explosion vent discs and vent pathways-target conventional weak points in the core assembly,were performed.A series of comparative arc flash tests were subsequently conducted to validate these modifications.Test re-sults indicate that the arc flash explosion process in current transformers comprises four distinct phases:sudden pressure rise,pressure accumulation,tearing,and explosion.Reasonably adjusting the burst disc threshold and the size of the oil tank connection channel can significantly reduce the energy release level.The modified current transformer demonstrates a 48.4%reduction in the fragmentation scatter range,with the kinetic energy of fragments restricted below 76 J/cm².The experimental methodology provides a reference for establishing arc-burning test standards,while the results furnish theo-retical support for enhancing the explosion-proof performance of current transformers.