一次风机RB控制逻辑优化与试验
Optimization and Experiment of RB Control Logic for Primary Air Fan
摘要 在某电厂新建 2×660 MW 燃煤机组启动调试中,发现一次风机选型时,一次风用户、阻力裕量考虑不足,导致单侧一次风机运行时出力偏紧.首先开展了单侧一次风机最大出力试验,然后优化了一次风机 RB 控制逻辑,制定了风险防范措施,最后在 450 MW 和 660 MW 工况下,完成了一次风机 RB 预备试验和正式试验.结果表明:一次风机 RB 触发后,隔离跳闸一次风机所在侧的空气预热器,可有效提高单侧一次风机出力;通过适当降低 RB 时锅炉主控指令目标值、加快给水指令下降速度、减小引风机开度指令优化RB 控制逻辑后,主要参数波动幅度良好,可为同类型机组一次风机 RB 试验成功实施提供有益借鉴.
Abstract:
During the startup commissioning of a new 2×660 MW coal-fired unit in a power plant,it was found that when the primary fan was selected,the primary air users and resist-ance margins were not sufficiently taken into account,resulting in tight output when the pri-mary fan was running on one side.Firstly,a maximum output test of the single-sided prima-ry fan was carried out,then the RB control logic of the primary fan was optimized and risk prevention measures were formulated,and finally the RB preparatory test and formal test of the primary fan were completed under 450 MW and 660 MW conditions.The results show that:after the primary fan RB is triggered,isolating the air preheater on the same side of the tripped primary air fan can effectively improve the primary fan output on one side;After opti-mizing the RB control logic by appropriately lowering the target value of the boiler main con-trol command at the time of RB,speeding up the descending speed of the water supply com-mand,and decreasing the induced draft fan opening command,the fluctuation of the main pa-rameters is good,and it can provide useful references for the successful implementation of the RB test of the primary fan of the same type of unit.
刊 名 锅炉技术 PKU
年,卷(期): 2026, 57(5)
分类号: TK323
机标分类号: TP302.2 TK223.23 TM621.2
在线出版日期: 2026年10月23日
基金项目: 5211DS24000P:国网浙江省电力有限公司科技项目,