摘要
新能源电力电子接口化导致系统频率主动支撑能力不足,借助有限的储能资源充分挖掘风电场频率主动支撑能力,对电网和新能源场站尤为重要.风机在最大功率跟踪(maximum power point tracking,MPPT)模式下仅靠转子动能释放进行一次调频,难以满足政策及标准规定的功率上调要求.为此,基于双馈感应风力发电机(doubly-fed induction generator,DFIG)的运行特性,给出风电机组转子动能输出极限计算方法,提出可增发容量指标以量化不同转速下DFIG的频率支撑能力.在此基础上,提出一种风储联合参与电网快速频率支撑的协调控制策略.在风储联合层面,优先由能量容量较大的储能提供基础有功支撑,当频率偏差较大、储能功率无法满足时,由风机释放转子动能补充峰值功率缺额;在风机层面,基于各机组可增发容量进行功率分配.仿真结果表明,在5 MW突增负载扰动下,无频率支撑时频率最低跌至49.88Hz.所提策略在储能配置仅1 MW的条件下仍可有效抬升频率最低点,相比纯储能策略(3 MW)将储能配置需求降低约67%,同时减少了风机偏离MPPT工作点造成的有功功率损失.
The frequency active support capability of power systems is insufficient due to the power-electronic interfacing of renewable energy generation.Leveraging limited energy storage resources to fully tap into the frequency active support capability of wind farms is particularly crucial for power grids and wind power plants.In the maximum power point tracking(MPPT)mode,wind turbines rely solely on the release of rotor kinetic energy for primary frequency regulation,which is difficult to meet the power increase requirements stipulated by policies and standards.Based on the operational characteristics of the doubly fed induction generator(DFIG,also known as doubly fed wind generator),a calculation method for the output limit of rotor kinetic energy of wind turbines is proposed,and an additional capacity index is introduced to quantify the frequency support capability of DFIG at different rotational speeds.On this basis,a coordinated control strategy for wind-storage joint participation in rapid frequency support of power grids is proposed.At the farm level,priority is given to energy storage with larger capacity to provide basic active power support.When the grid frequency deviation is large and the energy storage power cannot meet the demand,wind turbines release rotor kinetic energy to supplement the peak power shortfall.At the unit level,power distribution among wind turbines is based on the additional generating capacity of each unit.Simulation results show that under a 5 MW sudden load disturbance,the frequency drops to a minimum of 49.88 Hz without frequency support.The proposed strategy can still effectively raise the frequency minimum point with only 1 MW energy storage configuration,reducing the energy storage requirement by approximately 67%compared with the pure energy storage strategy(3 MW),while reducing the active power loss caused by wind turbines deviating from the MPPT operating point.