摘要
大直径短粗拉索的抗弯刚度和端部约束效应较为显著,传统三点弯曲方法及其常用测量装置难以兼顾检测精度、承载能力和现场便携性,尚缺乏适用于既有结构的便捷现场索力检测手段.为解决上述问题,首先面向高空、空间受限和大横向荷载条件研发外置式三点弯曲索力测量装置,采用拓扑优化、工程化构型重构、材料与尺寸寻优及装配体有限元分析相结合的方法对核心支撑架进行设计;在此基础上,采用考虑拉索抗弯刚度和端部索段长度影响的连续梁三点弯曲模型,并通过物理试验标定拉索等效抗弯刚度.装置最终采用 Q960 高强钢"封闭壳体+内部桁架式交错加劲肋"支撑架,测试跨距为 1 200mm、总高度为 265mm、核心承力板厚为 5mm;在 150kN 设计横向荷载作用下,装置最大 Mises 应力为 464MPa,各关键部件均处于弹性工作范围,同时采用底部承压构件相对位移表征拉索跨中挠度,以减小装置自身变形对测量结果的影响.以包商银行商务大厦 GS1 和 GS2 幕墙拉索为对象开展现场检测,除个别低索力工况受装置自重、初始接触状态和小荷载读数波动影响外,其余拉索实测索力与设计理论值的偏差均不超过 7.1%.结果表明,研发的测量装置与连续梁三点弯曲索力计算方法能够较好地适应大直径幕墙短粗索的现场检测条件,拓展了三点弯曲法由细长柔性索向大直径短粗索检测的适用范围,可为既有预应力幕墙索结构的运营期抽检和安全评估提供技术参考.
Large-diameter cables with low slenderness ratios exhibit significant bending stiffness and end-constraint effects.Conventional three-point bending methods and commonly used measuring devices cannot readily satisfy the simultaneous requirements of measurement accuracy,load-carrying capacity,and field portability,and effective in-situ methods for assessing cable forces in existing structures remain limited.To address this issue,an external three-point bending device was first developed for high-altitude operation,restricted working spaces,and large transverse loads.The supporting frame was designed through topology optimization,engineering reconstruction,material and dimensional optimization,and finite-element verification of the complete assembly.A continuous-beam three-point bending model accounting for cable bending stiffness and the lengths of the end cable segments was then adopted,while the equivalent bending stiffness of the tested cables was determined through physical calibration.The final device employed a Q960 high-strength steel supporting frame consisting of a closed shell and internal staggered truss stiffeners,with a test span of 1 200mm,an overall height of 265mm,and a 5mm-thick core load-bearing plate.Under the design transverse load of 150kN,the maximum von Mises stress was 464MPa,and all key components remained within the elastic range.The relative displacement of the bottom bearing component was used to represent the cable midspan deflection,thereby reducing the influence of device deformation on the measurements.Field tests were conducted on GS1and GS2 curtain-wall cables in the Baoshang Bank Commercial Building.Except for an individual low-force condition affected by device self-weight,initial contact conditions,and fluctuations in low-load readings,the deviations between the measured cable forces and the theoretical design values were within 7.1%.The results demonstrate that the developed measuring device,combined with the continuous-beam three-point bending method,is suitable for the in-situ force measurement of large-diameter curtain-wall cables with low slenderness ratios.The proposed approach extends the applicability of the three-point bending method from slender flexible cables to large-diameter low-slenderness cables and provides a technical reference for periodic inspection and safety assessment of existing prestressed curtain-wall cable structures.