Against the backdrop of the"dual carbon"goals and the construction of new-type power systems,broadband oscillations induced by high-penetration photovoltaic(PV)integration into weak grids have become increasingly prominent,posing a critical bottleneck to the secure grid connection of renewable energy.In view of the complex oscillation mechanisms,fragmented modeling approaches,and the lack of a unified identification framework in PV-dominated weak grids,this paper proposes an integrated"mechanism-modeling-identification"unified framework.First,the coupling paths involving phase-locked loops(PLLs),constant power control,LCL filters,and digital control delays,as well as the formation mechanisms of oscillations across different frequency bands,are systematically sorted out.Second,the applicability boundaries of three categories of modeling methods-small-signal modeling,impedance modeling,and time-domain/electromagnetic transient modeling are compared.Third,four types of identification methods are summarized,namely signal decomposition,energy quantification,data-driven approaches,and source-localization visualization.Finally,future directions are discussed,including unified modeling,mechanism-constrained online identification,and standardized engineering implementation.Comprehensive analysis demonstrates that establishing a unified framework bridging"mechanism-modeling-identification"can provide theoretical support for active monitoring and oscillation damping in PV-dominated weak grids,and holds significant reference value for the secure and stable operation of new-type power systems.