军事知识服务平台
非平稳与非高斯风场下导线风偏响应特性研究
Wind-induced swing response characteristics of transmission conductors under non-stationary and non-Gaussian wind fields
摘要 为揭示强对流天气下非平稳与非高斯风场对导线风偏响应的影响,以浙江省某500 kV线路风偏事故为背景,建立导线-跳线-绝缘子串耦联有限元模型,结合Vicroy时变平均风模型、演化谱理论和Hermite变换方法,构建典型的非高斯风场和具有下击暴流特征的非平稳风场,采用有限元时域法开展导线风偏动力学分析,并从频域能量分布角度探讨其响应特性.结果表明:在偏度1.0、峰度7.0的强非高斯性条件下,风场非高斯性仅使最大风偏角增大2.3%;非平稳性是风偏响应放大的主导因素,可使最大风偏角增大20.5%,时变平均风速快速上升和脉动风速方差时变波动共同放大导线低频背景响应.研究成果可为非平稳风场下输电导线抗风设计与风偏校核提供参考.
Abstract:
To clarify the effects of non-stationary and non-Gaussian wind fields on the wind-induced swing response of transmission conductors during severe convective weather,a coupled finite element model of conductors,jumpers,and suspension insulator strings was developed based on a wind-induced swing flashover event on a 500 kV transmission line in Zhejiang Province.Typical non-Gaussian wind fields and downburst-like non-stationary wind fields were generated using the Vicroy time-varying mean wind model,evolutionary spectral theory,and the Hermite transformation.Time-domain finite element analyses were then performed,and the response characteristics were examined in terms of frequency-domain energy distribution.The results show that,in the investigated strongly non-Gaussian case with a skewness of 1.0 and a kurtosis of 7.0,non-Gaussianity increases the maximum swing angle by only 2.3%.By contrast,non-stationarity is found to be the dominant factor in response amplification,increasing the maximum swing angle by 20.5%.The rapid increase in the time-varying mean wind speed and the time-varying fluctuation of fluctuating wind speed variance jointly amplify the low-frequency background response of the conductor.These findings provide a reference for wind-resistant design and wind-induced swing assessment of transmission conductors under non-stationary wind fields.
刊 名 振动与冲击 ISTICEIPKU
年,卷(期): 2026, 45(20)
分类号: TM75 TU312+.1
机标分类号: O211.63 P425.1 U448.27
在线出版日期: 2026年11月3日
基金项目: B311DS25Z006:国网浙江省电力有限公司科技项目,